Megger B10E AC/DC Voltage Power Supply
Includes: Cable set GA-00032, Transport case GD-00182 & Megger B10E instruction manual.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
The Megger B10E Power Supply Unit is used to supply voltage to the Circuit Breaker (CB) coils and spring-charging motor during installation and/or field service. Since the high-quality voltage available at the coil outputs is very load-independent, the power supplied resembles what is encountered under normal operating conditions. Circuit breaker functionality thus remains virtually unchanged. B10E enables you to test CB functions easily at the specified voltage levels.
The compact Power Supply Unit Megger B10E provides reliable assistance to those who do maintenance on high-voltage breakers. The control panel's intuitive layout makes it easy to operate, and the built-in thermal cutout and overload protector make it safe to use. The Megger B10E has been developed in collaboration with breaker manufacturers and testing personnel.
FEATURES
Reliable and stable power supply for circuit breaker testing.
Continuously variable 24-250 V AC or DC output.
Separate outputs for close coil, trip coil and spring charging motor voltage.
Direct triggering for minimum trip voltage testing.
Operate with a breaker analyser for efficiency in testing sequence.
Environment | |||
Application field | For use in medium and high-voltage substations and industrial environments. | ||
Operating temperature | 0 to 50°C (32 to 122°F). | ||
Storage | -40 to +70°C (-40 to +158°F). |
||
Humidity | 5% to 95% RH, non-condensing. |
||
CE-Marking | |||
LVD | 2006/95/EC. | ||
EMC | 2004/108/EC. | ||
General |
|||
Mains voltage | 115 / 230 V AC, 50/60Hz. | ||
Power consumption | 3300W. | ||
Protection | Thermal cut-outs, +80°C (+176°F) Short-circuit protectors at DC outputs. |
||
Display | LED. | ||
Measurement - Voltmeter - digital |
|||
Range | 0 – 300 V DC, 0 – 300 V AC. | ||
Resolution | 1 V. | ||
Inaccuracy | ±1% of displayed value, DC ±2.5% of displayed value, AC. |
||
Current shunt | 5 A / 50 mV ±0.5% (built-in). | ||
Test Lead Set, with 4mm Stackable Safety Plugs | 2 x 0.25 m (0.8ft), 2.5 mm² 2 x 0.5 m (1.6ft), 2.5 mm² 8 x 2 m (6.6ft), 2.5 mm². |
||
Dimensions | Instrument: 350 x 270 x 220 mm (13.8 x 10.6 x 8.7 inches) Transport case: 610 x 290 x 360 mm (24.0 x 11.4 x 14.2 inches). |
||
Weight | 20.8 kg (45.8lbs) 29.3 kg (64.6lbs) with accessories and transport case. |
||
Megger B10E warranty | One year. |
Outputs (DC) CAT II Coil, Closing/Breaking |
||
---|---|---|
Output Voltage | 24-300 V DC | |
Load Interval | Max 1s (at currents over 50mA) | |
Ripple | 2% peak-to-peak of the preset voltage | |
No-Load Voltage | Current | Load Dependency |
24 V | 10 A | <6% |
48 V | 10 A | <3% |
110 V | 7.9 A | <2% |
250 V | 3 A | <2% |
300 V | 1.25 A | <2% |
Outputs (AC), CAT II Coil, Closing/Breaking |
||
Output Voltage | 24 to 300 V AC | |
Load Current | Max 5 A | |
Load Interval | Max 30 min |
Output DC, CAT II Motor |
|||
---|---|---|---|
Output Voltage | 24 to 300 V DC (loaded) | ||
Open Circuit Voltage | Current | Load Voltage | Max Load Interval |
44 V | 18 A | 24 V | 20s |
48 V | 12 A | 40 V | 60s |
48 V | 18 A | 30 V | 20s |
120 V | 12 A | 90 V | 60s |
120 V | 18 A | 70 V | 20s |
240 V | 6 A | 200 V | 60s |
240 V | 9 A | 185 V | 20s |
Max Voltage: Terminals to Protective Earth (Ground) | |
---|---|
Terminal | Voltage |
Coil Closing, AC/DC | 300 V AC |
Coil Breaking, AC/DC | 300 V AC |
Motor | 250 V AC |
Shunt | 250 V AC |
Trigger Closing | 250 V AC |
Trigger Breaking | 250 V AC |
Cable Set | Standard Cable Set. | GA-00032 | |
Case | Transport case. | GD-00182 |