Chauvin Arnoux CA6424 Earth Tester
Includes: 6 rechargeable NiMH batteries, 1 carrying bag, 1 mains-USB adapter (5V, 2A), 1 USB-shaver cord, 1 multilingual getting started guide.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
Rugged and waterproof, the Chauvin Arnoux CA 6424 earth tester can be used for 2P and 3P earth measurements in total safety. Text markings and colour coding help users to avoid connection errors. It can also measure the voltage up to 600 V. All the measurements and functions are directly accessible on the front panel, even when wearing gloves.
Special connection technology for the G72 clamp allows measurement of the line (phase) current and leakage current, from 0.5 mA to 60 A. There is a dedicated key for cable compensation. A LED indicates when a hazardous voltage is present, while the NOISE symbol flashes to indicate when a noise voltage is present.
Equipped with a 3-display backlit screen, the CA 6424 ohmmeter lets you view all the useful information on a single screen: measurement result, errors concerning the measurements or the recorded values, as well as complementary information (USE, HR, etc.).Designed with safety in mind, the moment a hazardous voltage is detected, an LED lights up and measurement is prohibited. The connections have text marking and colour coding to help prevent mistakes as an added safety feature.
FEATURES
2P resistance / 3P earth measurements up to 50 kΩ in high-resistivity terrain.
Voltage measurement up to 600 V and RH stake resistance measurement.
Automatic stabilization of the measurement.
Help with positioning the stakes – average and 52%/62%/72% deviation.
Leakage current measurement from 0.5 mA.
Battery recharging via the mains, USB socket or vehicle cigarette lighter.
Instrument Functions | ||
---|---|---|
C.A 6422 | C.A 6424 | |
Earth resistance measurement (with three rods) | ||
Voltage measurement | ||
Resistance measurement | ||
Mean of the earth measurements at 52, 62 and 72% | ||
Detection of RH too high | ||
Detection of RE too high | ||
Detection of a spurious voltage on USE | ||
Measurement of AC current with an ammeter clamp (optional) |
Voltage | |
---|---|
Range | 0.1-600 V. |
Resolution | 0.1 V. |
Accuracy | ± (1%R + 1 ct). |
2P Resistance | |
Range | 0.05 - 99.99 Ω / 80.0 - 999.9 Ω / 0.800 - 9.999 kΩ / 8.00 - 50.00 kΩ. |
Resolution | 0.01 Ω / 1 Ω / 10 Ω / 100 Ω. |
Accuracy | ± (2%R + 10 cts) / ± (2%R + 2 cts) / ±(2%R + 1 ct) / ± (2%R + 1 ct). |
Cable compensation | up to 5 Ω. |
3P Earth Resistance | |
Range | 0.5 Ω - 50.00 kΩ. |
Resolution | 0.01 Ω / 0.1 Ω / 1 Ω / 10 Ω. |
Accuracy | ±(1%R + 10 cts) / ±(1%R +2 cts) / ±(1%R + 1 ct). |
Measurement frequency | 128 Hz or 256 Hz. |
No-load voltage | ±10 V peak. |
Measurement mode | One-shot or permanent. |
Data storage | Registers: RE @ 62%; RE @ 52%; RE @ 72%. |
Calculation of average | Calculation of the average and the % deviation in relation to the average. |
RH Stake Resistance Measurement | |
Range | 0.05-9.999 kΩ / 8 - 49.99 kΩ. |
Resolution | 1 Ω / 10 Ω. |
Accuracy | ±(10%R + 1 ct). |
USE Voltage Measurement | |
Range | 0.10 - 99.99 VAC / 80.0 - 600 VAC. |
Resolution | 0.01 V / 0.1 V. |
Accuracy | ±(2%R + 2 cts). |
Current Measurement (via optional G72 clamp) | |
Range | 0.5 - 999.9 mA / 0.800-9.999 A / 8.00-60.00 A. |
Resolution | 0.1 / 1 / 10 mA. |
Accuracy | ±(1%R + 4 cts) / ±(1%R + 2 cts). |
General Specifications | |
Display | Backlit custom 206-segment LCD. |
Measurement mode | V, I, R 2P (Ω), R 3P (Ω). |
Power supply | 6 x NiMH rechargeable batteries, charging time approx.. 6 hrs. |
Charger | Internal via mains/USB adapter supplied. |
Automatic power-off | Deactivatable. |
Battery life | >1,500 x 3P earth measurements at 100 Ω. |
Dimensions | 223 x 126 x 70 mm. |
Weight | 1 kg. |
Environment | Operation: -10 to +50°C / Storage: -40 to +70°C (without batteries/accumulators). |
Protection | Up to 600 V on any of the input terminals. |
IP/IK index | IP 65 as per IEC 60529 / IK 04 as per IEC 50102. |
Drop test | 1 metre as per IEC 61010-1. |
Standards / electrical safety | EMC: IEC 61326-1; IEC 61010-2-030 / 600 V CAT IV. |
Compliance with IEC 61557 | IEC 61557-1 and IEC 61557-5. |
Chauvin Arnoux C.A 6424 warranty | 24-months. |
COMPONENT |
DESCRIPTION | PART No. | ||
Carry Bag | Shoulder bag. | P01298006 | ||
Earth Kit 15m | 15m earth kit (Blue/Green/Red). | P01102017 | ||
Earth Kit 50M | 15m 3P Earth test kit. | P01102021 | ||
Clamp | Current clamp G72. | P01120872 |