- settings_phone Telephone: 02890 830302
- mail belfast@cuthbertsonlaird.co.uk
- EUR €
- GBP £
Megger DET14C Digital Earth Clamp
Product shown at manufacturers RRP. Click on 'Best Price Quote' button or telephone (Belfast) 02890 830302 for our sale price.
Includes: Megger DET14C Digital Earth Test Clamp-on Meter, Carry case with strap, User guide, Calibration check & 4 x AA batteries.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
The Megger DET14C represents a new generation of earth / ground clamp-on resistance testers. These instruments induce a test current into earth systems and measure ground resistance in multi-ground installations without needing to disconnect the ground.
Designed with flat core ends they prevent dirt build up, ensuring measurement integrity and improved reliability over products with interlocking teeth. Other enhancements over current generation products include improved accuracy and up to 300% increase in battery life.
The DET is rugged, compact and has configurable audible alarms. Additional features include a configurable auto shutdown, data storage, self-calibration on power up and a calibration loop - all contained in a sturdy Megger carry case.
FEATURES
Low maintenance flat jaw interface.
Measures ground resistance from 0.05 Ω to 1500 Ω.
Measures true RMS ground leakage current from 0.5 mA rms to 35 A rms.
CAT IV 600 V safety rating.
Backlit LCD display.
Resistance Measurements | ||
---|---|---|
Ground Resistance Range |
Resolution | Intrinsic Certainty |
0.05 to 0.99 Ω | 0.01 Ω | ±1.5% ± 0.05 Ω |
1.00 to 9.99 Ω | 0.01 Ω | ±1.5% ± 0.1 Ω |
10.0 to 99.9 Ω | 0.1 Ω | ±2% ± 0.5% |
100.0 to 199.9 Ω | 0.1 Ω | ±5% ±1 Ω |
200 to 400 Ω | 1 Ω | ±10% ±10 Ω |
400 to 600 Ω | 1 Ω | ±10% ± 10 Ω |
600 to 1200 Ω | 10 Ω | ±20% |
1200 to 1500 Ω | 10 Ω | ±35% |
Frequency of measurement 1390 Hz. | ||
Alarm Settings | ||
Alarm Type | Range | Resolution |
Threshold 1 | 1 to 1500 Ω | 1 Ω |
Threshold 2 | 1 to 1500 Ω | 1 Ω |
Current Measurements (RMS) | ||
Current Range | Resolution | Intrinsic Certainty |
0.5 mA to 0.99 mA | 0.01 mA | ±2% ± 0.05 mA |
1.00 to 9.99 mA | 0.01 mA | ±2% ± 0.05 mA |
10.0 to 99.9 mA | 0.1 mA | ±2% ± 0.1 mA |
100 to 999 mA | 1 mA | ±2% ± 1 mA |
1 to 9.99 A | 0.01 A | ±2% ± 0.01 A |
10 to 35 A | 0.1 A | ±2% ± 0.1 A |
True RMS readings up to a crest factor of 5.0 (peak current of 40 A) Accuracy guaranteed for 50 Hz and 60 Hz Measurement over the range 16 Hz to 400 Hz Maximum current is 100 A RMS continuous and 200A RMS for 60s max at 50 Hz and 60 Hz. |
||
General Specifications | ||
Maximum Jaw Opening | 39 mm. | |
Maximum Jaw Inner Dimensions | 39 mm x 55 mm. | |
Display Type | 4 + 6 digit with backlight. | |
Battery Type | 4 x 1.5 V IEC LR6/AA alkaline. | |
Battery Life | 24 hours continuous testing. | |
Auto Power Down | 300s (reset by jaw action or button press). | |
Datalogging | 256 records. | |
Range Selection | Automatic within each mode. | |
Sample Time | <1s. | |
Hold Function | Yes with visual indicator. | |
Alarm Function | Yes with visual indicator. | |
Warning Buzzer | ||
Operating Temperature and Humidity | -20 to 50°C, <85% RH. | |
Storage Temperature and Humidity | -40 to 60°C, <75% RH. | |
IP Rating | IP30 with jaws closed. | |
Performance | IEC 61557-5 IEC 61557-13 Class 1. |
|
Safety | EN 61010-2-032 CAT IV 600 V Pollution degree 2. |
|
EMC | Class B compliant, IEC 61326, BSEN 61326. | |
Dimensions | 248 x 114 x 49 mm (L x W x H). | |
Weight | 985 g. | |
Megger DET14C warranty | 1 year. Extended warranty conditional on registering. |