1742 Power Logger |
1746 Power Logger |
1748 Power Logger |
||
FUNCTIONS | ||||
Voltage, current, power, power factor, frequency | ||||
Energy forward/reverse | ||||
Peak Demand | ||||
THD | ||||
Voltage and current harmonics (to 50th)1
|
||||
Flicker | ||||
Unbalance1
|
||||
Rapid voltage change events1
|
||||
Interharmonics (to 50th)1
|
||||
Dips, swells, interruption and transient events tables1
|
||||
Mains signaling1
|
||||
Inrush current1
|
||||
Transients (low frequency)/Waveform deviation events2
|
||||
RECORDING | ||||
Trend
|
||||
Waveform snapshots2
|
||||
RMS profile2
|
||||
COMMUNICATION | ||||
Ethernet
|
||||
USB (mini B)
|
||||
WiFi download Instrument to device | ||||
Wifi download via WiFi hub (requires registration) | Opt. | Opt. | Opt. | |
1Included with 1742-6/UPGRADE option. 2Included with 1742-8/UPGRADE or 1746-8/UPGRADE option. |
Voltage | Range: 1000 V Maximum resolution: 0.1 V. |
|
Current: Direct input | See datasheet. | |
Frequency | Range: 42.5 Hz to 69 Hz Maximum resolution: 0.01 Hz. |
|
Auxiliary input | Range: ±10 V dc Maximum resolution: 0.1 mV. |
|
ELECTRICAL SPECIFICATIONS | ||
Power Supply | ||
Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit. 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7). |
|
Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter). | |
Mains power frequency | 50/60 Hz ±15%. | |
Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable. | |
On-battery runtime | Typically 4 hours. | |
Charging time | < 6 hours. | |
Data Acquisition | ||
Resolution | 16-bit synchronous sampling. | |
Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency. | |
Input signal frequency | 50/60 Hz (42.5 to 69 Hz). | |
Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φ wye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies). | |
Data storage | Internal flash memory (not user replaceable). | |
Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events. | |
Basic Interval | ||
Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy. | |
Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min. | |
Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms). | |
Demand Interval (Energy Meter Mode) | ||
Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy. | |
Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off. | |
Power Quality Measurements | ||
Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation. | |
Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT). |
|
Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only. |
|
Interharmonics | 1st to the 50th interharmonic. | |
Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency). |
|
Inrush | RMS profile based on 1/2 cycle RMS steady state triggering. | |
Flicker | In accordance with IEC 61000-4-15 and IEEE 1453. | |
Programmable PQ limits | Enables user defined limits for local standards compliance. | |
Interfaces. | ||
USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA. | |
WiFi | File transfer and remote control via direct connection or WiFi infrastructure. | |
Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or WiFi/BLE adapter, check for availability). | |
USB-mini | Data download device to PC. | |
Voltage Inputs | ||
Number of inputs | 4 (3 phases referenced to neutral). | |
Maximum input voltage | 1000 Vrms, CF 1.7. | |
Input impedance | 10 MΩ. | |
Measurement category | 1000 V CAT III/600 V CAT IV. | |
Current Inputs | ||
Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor. | |
Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8. Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range. |
|
Auxiliary Inputs | ||
Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously). | |
Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s. | |
Displayed units | User configurable (7 characters, for example, °C, psi, or m/s). | |
General Specifications | ||
Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1. | |
Enclosure | IEC 60529: IP50. IEC 60529: IP65 with IP65 rated voltage connector. |
|
1Warm up the product to -10 °C (+14 °F) before you power the unit on | ||
Weight | Instrument: 1 kg (2.2 lb). | |
Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in). | |
Fluke 1742 warranty | Two-years (battery not included). Accessories: one-year. |