The CT-3A is specifically designed to accurately monitor one, two or three current channels allowing you to monitor the loading and/or balancing problems and energy consumption of an installation.
The current levels are stored with dates and times. With the back-up battery, the Electrocorder can continue to record for 2 months. An external 12Vdc PSU input is available, to allow for prolonged logging without batteries.
The recorded data is uploaded to a PC via the supplied USB lead. Using Electrosoft, the recorded current levels, with dates and times that can be viewed in both tabular and graphical form, exported to a spreadsheet or saved to file. Graphs can be printed showing the recorded levels and the allowable tolerance bands.
The CT-3A-RS has two user selectable current ranges 0.5Aac to 40Aac and 4Aac to 400Aac. If you require a higher current ranges of up to 3kAac, consider the EC-3A-RS.
FEATURES
Three current channels c/w selectable range. CT’s fit round 30mm cables. Data stored in non-volatile memory. Selectable averaging period from 1 second to 60 minute. Complete with Electrosoft energy analysis software.
Electrocorder CT-3A-RS Specifications:
Current input socket types (all channels): 4 pin shrouded plugs and sockets.
Supplied current sensor: CAT II 600V, with 1mVac output per 1Aac input, 30mm aperture.
Supplied current sensor output: 1mVac per 0.1Aac input.
Sampling frequency (all channels): 16 samples per cycle 800Hz @ 50Hz or 960Hz @ 60Hz.
Data recorded: Average, max & min current values during the averaging period.
Memory capacity: 192kB able to record 32,000 current levels per channel/phase.
Memory type: Non-volatile SEEPROM.
Memory: 1 sec - 60 mins (1 sec gives 2 hrs of logging, 60 mins gives 300 days).
Current sensor input lead length: Metric 1.2 metres Imperial/English 4’ (4 feet).