Includes: testo 327 Flue Gas Analyser, rechargeable battery and calibration protocol, Flue Gas Probe (180mm x 6mm diameter), Differential hose kit, Differential temperature kit, testo infrared printer (0554 0547), carry case.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
The Testo 327-1 Advanced Kit combustion flue gas analyser is extremely robust and simple to use. Ideal for installation, commissioning, service and maintenance on all types of boilers and burners, tt measures combustion efficiency, °C, O2, CO2, CO and flue draught. The Testo 327 features simple to follow menus, a large 4 parameter display and fast startup (stable readings available within 30 seconds).
The tough, ergonomic design features a shock-proof elastomeric protection skin and modular probe connection system which is compatible with the Testo 330 range of probes.
FEATURES
Temperature - TC Type K (NiCr-Ni) | |
Measuring range | -40.00 to +600.00 °C. |
Accuracy | ±0.50 °C (0 to 99.90 °C) ±0.50 % of mv (100 to 600 °C. |
Resolution | 0.1 °C. |
Reaction time | < 50 s. |
Temperature (ambient temperature). | |
Flue gas O2 | |
Measuring range | 0 to 21 Vol.%. |
Accuracy | ±0.2 Vol.%. |
Resolution | 0.1 Vol.%. |
Reaction time t90 | 30 s. |
Differential Pressure flue gas Draught - Piezoresistive | |
Measuring range | -40.0 to +40.0 hPa ±0.03 hPa (-3.00 to +3.00 hPa. |
Accuracy | ±0.02 hPa (-0.50 to +0.60 hPa) ±0.03 hPa (+0.61 to +3.00 hPa) ±1.50 hPa (3.01 to +40.0 hPa. |
Resolution | 0.01 hP. |
Flue gas degree of effectivity, Eta (calculated) | |
Measuring range | 0 to 120 %. |
Resolution | 0.1 %. |
Flue gas loss (calculated) | |
Measuring range | 0 to 99.0 %. |
Resolution | 0.1 %. |
Flue gas CO2 calculation (calculated from O2) | |
Measuring range | 0 to CO₂ max (Display range). |
Accuracy | ±0.2 Vol.%. |
Resolution | 0.1 Vol.%. |
Reaction time t90 | < 40 s. |
Flue gas CO (without H2 -compensation) | |
Measuring range | 0 to 4000 ppm. |
Accuracy | ±20 ppm (0 to 400 ppm) ±5 % of mv (401 to 2000 ppm) ±10 % of mv (2001 to 4000 ppm). |
Resolution | 1 ppm. |
Reaction time t90 | 60 s. |
General technical data | |
Dimensions | 201 x 83 x 44 mm. |
Operating temperature | -5 to +45 °C. |
Display type | LCD (Liquid Crystal Display). |
Display function | Backlit 2-line display. |
Power supply | Battery: 1500 mAh, mains unit 5V/1A. |
Storage temperature | -20 to +50 °C. |
Weight | (with probe) Approx. 700 g. |
Battery | Spare rech. batt. w/ charging station testo 327 / testo 330-1/-2. | 0554 1087 | |
Quick Printer | Testo fast printer IRDA with wireless infrared interface; 1 roll thermal paper; 4 AA batteries. | 0554 0549 | |
Thermal Paper | Spare thermal paper for printer (6 rolls), permanent ink. | 0554 0568 | |
Cleaner | Instrument cleaner, 100 ml. | 0554 1207 | |
Smoke Tester | Smoke tester with oil; soot sheet; for measuring soot in flue gas. | 0554 0307 | |
Hose | Hose connection set for separate gas pressure measurement testo 327 / testo 330-LL. | 0554 1203 | |
Temperature Set | Differential temperature set consisting of 2 Velcro probes and temperature adaper testo 327. | 0554 1208 | |
Filter | Spare particle filter, 10 off. | 0554 3385 | |
Filter Paper | Spare soot filter paper; 8 paper rolls. | 0554 0146 | |
Case | System case flat. | 0516 3334 |