Includes: Continuity/earth bond lead Blow moulded caseEVA-T1 Type 2 to Type 1 connector adaptor.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
The Megger EVCC300 introduces a new and convenient way of checking Electric Vehicle charge points. A simple all in one concept provides an easy to use solution to check both the safety and operation of mode 2 and single phase mode 3 (level 1 and two phase level 2) EV chargers.
The instrument is ideal for those wishing to perform a check on an EV charge point as part of an inspection or maintenance programme.
FEATURES
EVSE Standard | IEC 61851-1:2017. |
EVSE Supply Options (set in settings) | 1. 230 V single-phase. |
2. 120 V single-phase. | |
3. 208 V two-phase. | |
4. 240 V two-phase. | |
Supply Measurement | |
Voltage range | 5 V to 300 V. |
Voltage resolution | 1 V. |
Voltage accuracy | ± 5% ± 2 digits. |
Voltage measurement | L to N, L to PE and N to PE. |
Reverse polarity indication | L to N, for single-phase option only. |
Frequency range | 45 Hz to 65 Hz. |
Frequency resolution | 1 Hz. |
Frequency accuracy | ± 1 digit. |
EVSE Interface (EV charger function) tests | |
1. Proximity detection (PP) states: Read only |
No proximity. |
Proximity detected, unlatched. | |
Proximity detected, latched. | |
2. Control pilot (CP) Set and read states: |
State A – Disconnected. |
State B – Connected. | |
State C – Charging. | |
State D – Charging without ventilation. | |
State E – CP short to PE. | |
Read-only state | State F – EVSE charger fault condition. |
Maximum voltage | ± 14 V. |
Frequency range | 940 Hz to 1040 Hz. |
Duty cycle range | 8% to 97%. |
Maximum charging current indication according to IEC 61851-1:2017, tables A.7 and A.8. | |
Resistance of Earth Protective Earth Protective Conductor (RPE) | |
Test current | 200 mA. |
Resistance range | 0 to 10 Ω. |
Resistance resolution | 0.01 Ω. |
Resistance accuracy | ± 5% ± 2 digits. |
RCD/GFCI Tests | |
Trip time accuracy | ± 1% ± 1 ms. |
Trip current accuracy | ± 3% (apply to all RCD/GFCI tests). |
Personal Protection Tests, 230V Single Phase | |
1. RCD 30 mA ac TEST | |
Test current | 31.5 mA AC (5% above nominal trip current). |
Max. test time | 300 ms. |
Polarity selection | 0° and 180° of an input sine wave. |
2. RCD 6mA dc Test | |
Test current ramp | up at rate of 6 mA in 2.5 s, then held at 6 mA DC. |
Ramp polarity | positive and negative ramp. |
Max. test time | 12.5 s. |
Polarity selection | 0° and 180° of an input sine wave. |
Personal Protective Tests, 120V Single Phase/ 240V Two Phase | |
1. GFCI/CCID 5 mA ac test | |
Test current | 6 mA AC. |
Max. test time | 5.59 s. |
Polarity selection | 0° and 180° of an input sine wave. |
2. GFCI/CCID 20 mA ac test | |
Test current | 21 mA AC (5% above nominal trip current). |
Max. test time | 5.59 s. |
Polarity selection | 0° and 180° of an input sine wave. |
Nuisance Tripping Tests, 230V Single Phase | |
1. RCD ac ramp test | |
Test current | AC current ramp up to 30 mA in 2 mA steps. |
Step time | 300 ms. |
Max. test time | 4.5 s. |
2. RCD dc ramp test | |
Test current ramp | up at rate of 6 mA in 2.5 s, then held at 3 mA DC. |
Max. test time | 11.25 s. |
Nuisance Tripping Tests, 120V Single Phase/ 240V Two-Phase | |
1. GFCI/CCID 5 mA AC test | |
Test current | AC current ramp up to 6 mA in 0.5 mA steps. |
Step time | 100 ms. |
Max. test time | 1.2 s. |
2. GFCI/CCID 20 mA AC test | |
Test current | AC current ramp up to 20 mA in 1 mA steps. |
Step time | 100 ms. |
Max. test time | 2 s. |
Touch Voltage Test | |
Options | 25 V or 50 V limit. |
Test current typically 1/3 of RCD nominal test current | |
Touch Contact Pad Test | Dangerous voltage indication at PE conductor. |
Power Supply | |
Battery | Four AA cells. |
Connections | Type 2 male – main test connection. |
4 mm shrouded socket on base of handle – RPE test return connection. |
|
Environment | |
Operational temperature | 0 ºC to 40 ºC. |
Storage temperature | -10 ºC to 70 ºC. |
Operating humidity | 90% R.H. at +40 °C max. |
Maximum altitude | 2000 m. |
Dust and moisture ingress | IP40 to IEC60529 in use. |
Safety | |
Standards | IEC 61010-1:2010. |
Safety category | CATII 300 V. |
Languages | |
User Interface | English, French, German and Spanish. |
User guide | English, French, German and Spanish. |
Dimensions and Weights | |
Dimensions (L x H x W) | 24 x 18 x 8.6 cm. |
Weight (without batteries) | 583 g. |