Includes: Fluke T6-1000 PRO Electrical Tester, Attached Test Leads with removeable probe caps, AC285 SureGrip™ Black Alligator Clip, H-T6 Holster, User Documentation.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
Function | ||
FieldSense AC voltage | Requires test leads | No |
Range | 1000 V | |
Resolution | 1 V | |
Accuracy | ±(3 % + 3 counts) 45 Hz - 66 Hz[1] [2] | |
FieldSense AC current | Requires test leads | No |
Range | 200.0 A | |
Resolution | 0.1 A | |
Accuracy | ±(3 % + 3 counts) 45 Hz - 66 Hz | |
FieldSense frequency (Hz) | Requires test leads | No |
Range | 45 Hz – 66 Hz | |
Resolution | 1 Hz | |
Accuracy | ±(1 % + 2 counts) | |
Volts AC | Requires test leads | Yes |
Range | 1000 V | |
Resolution | 1 V | |
Accuracy | ±(1.5 % + 2 counts) 45 Hz - 66 Hz | |
Volts DC | Requires test leads | Yes |
Range | 1000 V | |
Resolution | 1 V | |
Accuracy | ±(1 % + 2 counts) | |
Resistance | Requires test leads (all ranges) | Yes |
Range | 2000 Ω | |
Resolution | 1 Ω | |
Range | 20.00 kΩ | |
Resolution | 0.01 kΩ | |
Range | 100.0 kΩ | |
Resolution | 0.1 kΩ | |
Accuracy (all ranges) | ±(1 % + 2 counts) | |
Notes | Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC conversions are ac-coupled, RMS responding. | |
Accuracy[2]: FieldSense specified from 16V to 1000V. | ||
General Specifications | ||
Calibration | 1-year calibration cycle. | |
Dimensions | 61 mm x 259 mm x 43 mm. | |
Weight | 0.35 kg (0.78 lb). | |
Fork opening | 17.8 mm (0.7”). | |
Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F). |
Storage | -30 °C to +60 °C (-22 °F to +140 °F). | |
Altitude | Operating | 2,000 m (6,562 feet). |
Storage | 10,000 m (32,808 feet). | |
Relative Humidity | 0 % to 90 %, 5 °C to 30 °C (41 °F to 86 °F). | |
0 % to 75 %, 30°C to 40 °C (86 °F to 104 °F). | ||
0 % to 45 %, 40°C to 50 °C (104 °F to 122 °F). | ||
Battery | Type | 2x AA (IEC LR6). |
Life | 360 hour continuous, typical is 200 hour using the FieldSense function. | |
Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C (< 64.4 °F or > 82.4 °F). | |
Safety General | IEC 61010-1: Pollution Degree 2. | |
Measurement T6-1000 Pro | IEC 61010-2-032: CAT IV 600 V / CAT III 1000 V. | |
Electromagnetic Compatibility | IEC/EN 61326-1: Portable. |
COMPONENT PARTS | DESCRIPTION | PART No. | ||
TPAK | ToolPak, Meter Hanging Kit. | 1281997 | ||
PRV240FS | Proving Unit. | 4910310 | ||
TP1-1 | Probe Set, Flat-Blade (US/UK flat tip). | 3971265 | ||
AC285 | SureGrip Alligator Clips. | 1610159 |