- settings_phone Telephone: 02890 830302
- mail belfast@cuthbertsonlaird.co.uk
- EUR €
- GBP £
T&R PT18-10 mk3 DC Cable Test Systems
Product shown at manufacturers RRP. Click on 'Best Price Quote' button or telephone (Belfast) 02890 830302 for our sale price.
The T&R PT18-10 mk2 includes an automatic load discharge system that discharges the cable under test when the output is switched off or a breakdown occurs.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
The T&R PT18-10 Mk2 high voltage dc test set is designed to perform tests on installed cable and jointing systems. The units have a variable output voltage with a maximum of ±18kVdc with a maximum charging capability of 10mA. A zero-volt interlock is fitted that prevents the output being switched on unless the output control is at zero.
In the event of a test object failure, the overload circuit will automatically switch off the output voltage and earth the output via the internal discharge circuit. A manual discharge probe is also supplied as standard with the T&R PT18-10 mk2 unit, allowing higher load capacitance's to be safely discharged.
- Output: 0 to ±18kV, continuous at 5mA, 5mins at 10mA.
- Metering voltage: 0-20kV.
- Metering current: 1mA, 10mA.
- Supply requirements: 115V/240V, 50/60Hz, 1 ph, 600VA max.
- Protected by an overload trip on the output that operates at 12mA.
- Compliance: BS EN61010.
- Storage temperature: -20°C to 60°C.
- Operating temperature: 0°C to 45°C.
- Dimensions: 471 x 144 x 362mm.
- Weight: 17kg.
- T&R PT18-10 mk2 Warranty: One year.
Includes: 2m long supply lead, Spare 7A fuse, 2 x 5m long output leads, DP20 discharge probe, PT18-10 Mk2 Operating manual.