Includes: Megger MIT515 Insulation Tester, 3 x 3m Test Leads & Medium Insulated Clips, Calibration Certificate, Power Lead and MIT515 User Guide on CD.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
Offering CAT IV, the Megger MIT515 is the simplest of Megger's range of small, light 5 kV insulation resistance testers for the testing and maintenance of high voltage electrical equipment. Enclosed in a tough case it is both smaller and lighter than its predecessor making it even easier to carry and store.
Now equipped with lithium ion fast rechargeable batteries, the instrument has a large, clear, easy to read, display making it equally suitable for use in both bright sunlight and poorly lit environments. Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant.
The Megger MIT515, MIT525 and MIT1025 can be powered from the mains supply or by it’s rechargeable battery, which provides for 4½ to 6 hours of continuous testing with a 100 MΩ load, depending on model. The battery pack contains Lithium-ion cells and should be replaced when it no longer holds a charge. A new battery is available as a spare part from Megger. The battery pack is housed within a grey moulded cover secured by four screws. On no account must the transparent inner case be opened. Hazardous voltages up to 5kV will be exposed.
FEATURESSmall and light.
Measures up to 10 TΩ.
Selectable test voltage from 250 to 5000 V.
PI, DAR, DD test.
Improved productivity – operate from line power/mains if battery dead.
Li ion battery - extended capacity, rapid charge.
Mains / line operation even with totally dead battery.
Dedicated AC/DC voltage range with frequency (Hz) measurement.
Date and time stamped test results.
CATIV 600 V safety rating.
Tough dual case construction .
Fully specified guard terminal performance.
Test voltages |
250 V, 500 V, 1000 V, 2500 V, 5000 V, V Lock. | ||
Resistance range | 10 kΩ to 10 TΩ @ 5 kV. | ||
Lock Test Voltage | 100 V to 1 kV in 10 V steps 1 kV to 5 kV in 25 V steps. |
||
Guard Terminal Performance | Guards out parallel leakage resistance down to 250 kΩ with a maximum additional resistance error of 1% with a 100 MΩ load. | ||
Display | Analogue: 100kΩ to 10TΩ Digital: 10kΩ to max a above. |
||
Short Circuit/Charge Current | 3mA @ 5kV. | ||
Insulation Test | Alarm: 100kΩ to 10GΩ. | ||
Capacitor Charge | <3 s/μF at 3 mA to 5 kV. | ||
Capacitor Discharge | <120 ms/μF to discharge from 5000 V to 50 V. | ||
Capacitance Range (with voltage set above 500V) | 10 nF to 25 μF. | ||
Capacitance Measurement Accuracy | ±10% ±5 nF. | ||
Current Range | 0.01 nA to 6 mA. | ||
Current Accuracy | ± 5% ± 0.2 nA at all voltages (23°C). | ||
Interference | 3 mA from 450 V to 5 kV. | ||
Voltmeter range | 30 V to 660 V ac or dc, 45Hz – 65Hz. | ||
Timer range | Up to 99 minutes 59 seconds, 15 second minimum setting. | ||
Test modes | IR, IR(t), DAR, PI. | ||
Operating temperature range | -20 °C to 50 °C. | ||
Battery life | 6 hours (typical) continuous testing at 5 kV with a 100 MΩ load. | ||
Battery charge time | 2.5 hours deep discharge, 2 hours normal discharge. | ||
IP rating | IP65 (lid closed), IP40 (lid open). | ||
Dimensions | 315 x 285 x 181mm. | ||
Weight | 4.5kg. | ||
Megger MIT515 Warranty | 2 year. |