Includes: Tool bag containing, mains lead, 3 safety leads with HV croc clips, HV pick up lead & Chauvin C.A 6545 handbook.
Our pages are encrypted and protected from cyber-attack.
Payment Card Industry Data Security Standard (PCI DSS) Compliant.
TLS (SSL) - all data/information is secure from interception.
In a site-proof case, the Chauvin Arnoux C.A6545 megohmmeter makes a quantitative and qualitative analysis of insulation. It also automatically measures voltage, capacity and residual current. The multiple functions not only qualify the measured insulation, but also provide real preventative maintenance.
POLARISATION INDEX (PI) & DIELECTRIC ABSORPTION RATIO (DAR):
Insulation is sensitive to temperature and humidity variations. In addition, measurement is affected by the appearance of disturbance currents. To overcome these effects, long-term measurements must be performed and the PI and DAR coefficients must be calculated. They will then allow qualification of the insulants and their ageing.
DIELECTRIC DISCHARGE INDEX (DD):
This test measures the dielectric absorption of a heterogeneous or multi-layer insulant and will reveal the presence of impurities or a faulty layer.
TEST WITH PROGRAMMABLE DURATION
To deal with the whole range of measurement situations (electrical equipment, telecom installations, etc.) and measure as accurately as possible, the CA6545 offers the possibility of selecting the test voltage by means of the Var 50-5,000 V setting on the rotary switch. The voltage can be adjusted between 40 V and 1,000 V in 10 V increments and between 1,000 V and 5,100 V in 100 V increments.
FEATURES
Digital filtering of insulation measurements.
Automatic voltage measurement.
Automatic detection of the presence of AC or DC external voltage on terminals.
Threshold programming, to trigger alarms using audible beeps.
Timer for measurement time checks.
Protection of the device by fuse, with detection of defective fuses.
Automatic discharge of the residual high voltage on the equipment tested.
Automatic power save mode of the device to save battery power.
Indication of battery charge condition.
Large backlit LCD screen with a wide range of indicators.
Fixed test voltages | 500 V | 1000 V | 2500 V | 5000 V | |
Insulation ranges | 10 kΩ to 2 TΩ | 10 kΩ to 4 TΩ | 10 kΩ to 10 TΩ | 10 kΩ to 10 TΩ | |
Adjustable test voltage | 40 V to 5,100 V in 10 or 100 V increments. | ||||
Voltage | 1 to 5,100 V (15 Hz to 500 Hz or DC). | ||||
Capacitance | 0.001 to 49.99 F. | ||||
Leakage current measurement | 0.00 - 3mA. | ||||
Functions | |||||
Display | Large LCD screen. | ||||
Backlighting | |||||
Programmable alarms | |||||
Smoothing of display | |||||
Prog. test duration | |||||
Calculation of ratios | DAR - PI and DD. | ||||
Step voltage mode | |||||
Calc. of R at reference T° | |||||
Locking of test voltage | |||||
R(t) | Recording of samples. | ||||
Storage | |||||
RS 232 | |||||
Printing of measurements | |||||
PC software | |||||
Power supply | Rechargeable NiMH battery. | ||||
Battery life | 30 days with 10 DARs and 5 PIs / day. | ||||
Electrical safety | IEC 61010-1 (Cat. III 1,000 V or Cat. I 2,500 V) and 61557. | ||||
Dimensions (L x W x H) | 270 x 250 x 180 mm. | ||||
Weight | 4.3 kgs. | ||||
Chauvin C.A6545 warranty | 12 months. |
COMPONENT |
DESCRIPTION | PART No. | ||
Case | Standard Carrying Bag. | P01298066 | ||
HV leads | Set of 2 HV cables with safety connector 4mm (red/guarded black) 3m. | P01295231 | ||
Clips | Set of 2 alligator clips (red/black). | P01295457Z | ||
Tips | Set of 2 test contact tips (red/black). | P01295458Z |