loading spinner
Megger MIT515 5kV Insulation Tester
  • Megger MIT515 5kV Insulation Tester
  • Megger MIT515 5kV Insulation Tester
  • Megger MIT515 5kV Insulation Tester

Megger MIT515 5kV Insulation Tester

Megger approved distributor and service centre.

Includes: Megger MIT515 Insulation Tester, 3 x 3m Test Leads & Medium Insulated Clips, Calibration Certificate, Power Lead and MIT515 User Guide on CD.

£2,890.00
Tax excluded
Quantity
  HTTPS Secure

Our pages are encrypted and protected from cyber-attack.

  Compliant

Payment Card Industry Data Security Standard (PCI DSS) Compliant.

  Protected

TLS (SSL) - all data/information is secure from interception.

Offering CAT IV, the Megger MIT515 is the simplest of Megger's range of small, light 5 kV insulation resistance testers for the testing and maintenance of high voltage electrical equipment. Enclosed in a tough case it is both smaller and lighter than its predecessor making it even easier to carry and store.

Now equipped with lithium ion fast rechargeable batteries, the instrument has a large, clear, easy to read, display making it equally suitable for use in both bright sunlight and poorly lit environments. Information displayed includes resistance, voltage, leakage current, capacitance, battery status and time constant.

The Megger MIT515, MIT525 and MIT1025 can be powered from the mains supply or by it’s rechargeable battery, which provides for 4½ to 6 hours of continuous testing with a 100 MΩ load, depending on model. The battery pack contains Lithium-ion cells and should be replaced when it no longer holds a charge. A new battery is available as a spare part from Megger. The battery pack is housed within a grey moulded cover secured by four screws. On no account must the transparent inner case be opened. Hazardous voltages up to 5kV will be exposed.

FEATURES

Small and light.
Measures up to 10 TΩ.
Selectable test voltage from 250 to 5000 V.
PI, DAR, DD test.
Improved productivity – operate from line power/mains if battery dead.
Li ion battery - extended capacity, rapid charge.
Mains / line operation even with totally dead battery.
Dedicated AC/DC voltage range with frequency (Hz) measurement.
Date and time stamped test results.
CATIV 600 V safety rating.
Tough dual case construction .
Fully specified guard terminal performance.

Megger MIT515, MIT525 & MIT1025 Intro and Demonstration

Megger MIT515 Specifications:
Test voltages
250 V, 500 V, 1000 V, 2500 V, 5000 V, V Lock.
Resistance range 10 kΩ to 10 TΩ @ 5 kV.
Lock Test Voltage 100 V to 1 kV in 10 V steps
1 kV to 5 kV in 25 V steps.
Guard Terminal Performance Guards out parallel leakage resistance down to 250 kΩ with a maximum additional resistance error of 1% with a 100 MΩ load.
Display Analogue: 100kΩ to 10TΩ
Digital: 10kΩ to max a above.
Short Circuit/Charge Current 3mA @ 5kV.
Insulation Test Alarm: 100kΩ to 10GΩ.
Capacitor Charge <3 s/μF at 3 mA to 5 kV.
Capacitor Discharge <120 ms/μF to discharge from 5000 V to 50 V.
Capacitance Range (with voltage set above 500V) 10 nF to 25 μF.
Capacitance Measurement Accuracy ±10% ±5 nF.
Current Range 0.01 nA to 6 mA.
Current Accuracy ± 5% ± 0.2 nA at all voltages (23°C).
Interference 3 mA from 450 V to 5 kV.
Voltmeter range 30 V to 660 V ac or dc, 45Hz – 65Hz.
Timer range Up to 99 minutes 59 seconds, 15 second minimum setting.
Test modes IR, IR(t), DAR, PI.
Operating temperature range -20 °C to 50 °C.
Battery life 6 hours (typical) continuous testing at 5 kV with a 100 MΩ load.
Battery charge time 2.5 hours deep discharge, 2 hours normal discharge.
IP rating IP65 (lid closed), IP40 (lid open).
Dimensions 315 x 285 x 181mm.
Weight 4.5kg.
Megger MIT515 Warranty 2 year.
Megger
1001-935

Download

Megger HV Insulation Datasheet

PDF Specifications of the Megger MIT515, MIT525, MIT1025 & MIT1525 HV Insulation Testers.

Download (996.65k)

8 other products in the same category: